Instructions / Assembly

A2
Inverter (0.75-30kW)
Chapter 7 Description of Configure Parameters
Pn 01
Default display content1——30000
RUN 1 means it will display runtime frequency
Otherwise, it displays motor’s synchronization speed.
2——30000 is motor synchronization speed
STOP
it will display frequency given by external signal.
Pn 02
Pn 03
Initial startup frequency by panel or other method
Range
000.01Hz
400.00Hz
the initial panel data and
external signal frequency during startup
.
Source of runtime frequency with range1—7
1
3
5
7
Potentiometer
2 Panel button
4 External 0-10V signal
6 External digital signal
External 0-5V signal
External 0-20mA signal
Multi-segment signal
Pn 04
Pn 05
Source of runtime command with range1—2
Panel button control 2 External signal control
1
clockwise / anticlockwise disable with range
1—3
1
3
clockwise enable only
clockwise / anticlockwise enable
2 anticlockwise enable only
Pn 06
Pn 07
Method to stop inverter with range
1—2
stop by itself 2 stop by deceleration
1
Start again by external signal with range
1—2
disable 2 enable
1
Description: when the power on the external operation of
the signal is allowed to start effectively.
Pn 08
Acceleration time with range000.01S650.00S
Accelerate time (from 0Hz to Pn10).
1
2