MODEL RATING
LOAD PERCENT OF CAPACITY 500VA/300W 700VA/420W 1000VA/600W 1500VA/900W
10% 74 60 53 64
20% 33 27 22 37
25% 23 17 16 25
30% 21 15 14 23
40% 14 10 10 15
50% 8 8 7 11
60% 7 5 5 8
70% 5 4.5 4 6
75% 4.2 3.2 3.6 4.5
80% 4 3 3.5 4
90% 3 2.5 2.5 3.5
100% 2 2 2 3
Note: Run times in this table are approximate. They are based upon new, fully charged standard battery modules
at a temperature of 25 degC (77 degF) with 100% resistive UPS loading.