3.4 Audible-tone Indicators
TYPE INDICATES
1 beep every 10 seconds Battery mode
2 beeps every second UPS warning
2 beeps every 5 seconds Low-battery warning
3 beeps every 30 seconds Replace-battery warning
Constant, solid tone UPS fault
3-second tone followed by 2 beeps Power-on in battery self-test mode
1 long tone Power off
3 beeps Manual battery self-test
Table 3.3 Tones and Beeps of the UPS
3.5 Warnings
The UPS has three early-warning indicators that allow the UPS to function normally for a short period
before the outputs are shut-off.
ICON
DISPLAYED
AUDIBLE TONE DESCRIPTION SUGGESTED TROUBLESHOOTING
1 beep every second
Output-overload. The load devices
plugged-in to the UPS output are drawing
more power than the UPS rating.
Reduce the load to below the UPS rating in the specifications
table, see Specifications on page19.
Constant, solid tone
Site-wiringfault. Problem detected with the
outlet wiring to which the AC input of the
UPS is connected.
Power-off the UPS and contact an electrician to correct the
wiring. Possible causes are line and neutral are reversed or
there is no ground conductor.
3 beeps every 30
seconds
The battery is weak or damaged.
Charge the UPS battery for at least 12 hours, or replace the
battery, see Battery Replacement on page18.
Table 3.4 Warning Indicators and Actions