User's Manual

16 Versus Technology, Inc.
Leaving switch 1 in the ON position and moving switch 2 to the OFF position will cause a “tag-not-
seen” within 30 seconds to transmit the code to Wiegand Port 2.
Moving both switch 1 and 2 to the OFF position will cause the “tag-not-seen” ID within 60 seconds,
to be transmitted to Wiegand Port 2.
Measuring time in minutes instead of seconds
Moving switch 3 to the OFF position will change the “tag-not-seen” report to wait for minutes instead
of seconds, example 5, 15, 30 or 60 Minutes.
DIP Switch 4 is not used and must
be left in the ON position.
Switch 2 OFF,
switches 1, 3, and 4
ON.
Switches 1 and 2
OFF, switches 3
and 4 ON.
Switch 3 OFF
changes the wait
time from seconds to
minutes.
In this example, the wait time will
be 5 minutes until the “tag not
seen” signal is sent to Wiegand
port 2.
In this example, the wait time will
be 15 minutes until the “tag not
seen” signal is sent to Wiegand
port 2.