Operating instructions

16 20300293
Resolution Direct Vent Gas Fireplace
Max 20"
Max 20"
36"
(914 mm)
Max.
36"
(914 mm)
Max.
FP1177
max horizontal run
24”
(610 mm)







The Vent Graph, showing the relationship between vertical
and horizontal side wall venting, will help to determine the
various dimensions allowable. Figure 10





Z\x



         

When vent exits through foundations less than 20" below
outcrop, the termination must be ush up with outcropped
wall above.
It is best to locate the replace in such a way that minimizes
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the ue collar of the replace (or the top of the
Transition Elbow) to the face of the nished outside wall.
The maximum number of 9 elbows per side wall
installation is three (3). Figure 14
FP1176
max 90 bends
Figure 14 -
Maximum Three (3) 90° Elbows Per Installation
3 x 90°
Elbows
24" Min.
FP1176
FP1177
Figure 15 -
Maximum Horizontal Run with No Rise
If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36". Figure 16. This does not apply if the 90° elbows
are used to increase or redirect a vertical rise.
 According to the vent graph (Page 14) the maxi-
mum horizontal vent length in a system with a 10' vertical
rise is 17Z\x (5.2 m) and if a 90° elbow is required in the
horizontal vent it must be reduced to 14Z\x' (4.4 m).
In Figures 16 and 17 dimension A plus B must not be
greater than 14Z\x' (4.4 m).
A
B
10’
FP2133
Horizontal run
reduction
Figure 16 -
Horizontal Run Reduction
FP2133
A minimum of 24" is required before a 90° elbow. If a 90°
elbow is tted directly after 24" vertical section mounted
to the top of the replace, the maximum horizontal vent
run before the termination or a vertical rise is 36” (914
mm). Figure 15
90° Elbow = 36" (914
mm) Reduction