Specifications
TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A
D.O.I: 17/01/2008
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
6
Wiring Diagrams
Wiring Diagram – LHEC30 & RFSDV34
When installing the RFSDV34 the draught hood adapter (draught diverter)
supplied with the log fire MUST be installed. The draught diverter has an
inbuilt „blocked flue safety switch‟ which MUST be wired in series with
thermopile circuit 1 by the installing technician. The log fire must not be
operated unless the draught diverter is installed and the blocked flue switch
wired as per the installation instructions & wiring diagram shown below.
RFSDV34 wiring diagram as supplied and
before draught diverter installation.
RFSDV34 wiring diagram after draught
diverter installation & wiring (blocked flue
switch and flue switch wiring shown in red).