Specifications

TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A
D.O.I: 17/01/2008
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
44
Burner Feed Pipe RFSDV34 (Procedure 29)
1. Remove the burner (refer to procedure 27).
2. Unscrew burner feed pipe nut at gas valve and remove burner feed pipe from gas
valve.
3. Remove heat resistant sealing compound from burner feed pipe aperture in log fire
base.
4. Remove retaining screw holding burner manifold bracket to log fire base and withdraw
burner manifold and burner feed pipe through aperture in log fire base.
5. Unscrew burner feed pipe nut at burner manifold and remove burner feed pipe from
burner manifold.
6. Complete reassembly in reverse order of above ensuring burner feed pipe aperture in
log fire base is sealed with heat resistant sealing compound (part number 890591).
7. Test for gas leaks at all unions using soapy water solution.
Burner Manifold RFSDV34 (Procedure 30)
1. Remove burner feed pipe (refer to procedure 29).
2. Unscrew and remove front and/or rear burner injector(s).
3. Unscrew and remove burner manifold to burner feed pipe adapter.
4. Complete reassembly in reverse order of above using gas sealing paste on burner
injector threads and burner manifold to burner feed pipe adapter.
5. Test for gas leaks at all unions using soapy water solution.
Gas Valve RFSDV34 (Procedure 31)
Wear Personal Protective Equipment when conducting step 2 of this
procedure to reduce the risk of electric shock. Refer to Rheem Safety
Procedure on electrical testing.
1. Isolate power and gas supplies to the log fire and remove front lower access panel
(refer to procedure 21).
2. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the transformer that voltage is not present.
3. Remove glass frame assembly (refer to procedure 1).
4. Remove log assembly and larva rock from burner (reverse procedure 20).
5. Mark and disconnect all gas valve wiring. Note: Mark wiring to ensure thermopiles
and components are reconnected in their original location.
6. Disconnect ignition plug wiring by unplugging at electrical joining connector.
7. Unscrew pilot feed pipe nut at gas valve and remove pilot feed pipe from gas valve.
8. Unscrew burner feed pipe nut at gas valve and remove burner feed pipe from gas
valve.
9. Remove two screws retaining gas valve supporting bracket to log fire base and remove
gas valve.
10. Remove four screws retaining gas valve supporting bracket to gas valve.
11. Complete reassembly in reverse order of above.
12. Test for gas leaks at all unions using soapy water solution.
13. Operate log fire and perform the gas valve safety shutdown test procedure (refer to
page 18).
14. Operate log fire and perform remote controller recognition procedure (refer to
„Recognition Signal‟ on page 12).