Specifications

TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A
D.O.I: 17/01/2008
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
39
Gas Valve LHEC30 (Procedure 13)
1. Remove the sheet metal base (refer to procedure 3).
2. Mark and disconnect all gas valve wiring. Note: Mark wiring to ensure thermopiles
and components are reconnected in their original location.
3. Disconnect ignition plug wiring by unplugging at electrical joining connector.
4. Unscrew pilot feed pipe nut at gas valve and remove pilot feed pipe from gas valve.
5. Unscrew burner feed pipe nut at gas valve elbow and remove burner feed pipe from
gas valve.
6. Remove four screws retaining gas valve to gas valve supporting bracket and remove
gas valve.
7. Unscrew and remove burner feed pipe elbow from gas valve.
8. Complete reassembly in reverse order of above using thread tape on gas valve elbow
and check for gas leaks using soapy water solution.
9. Operate log fire and perform the gas valve safety shutdown test procedure (refer to
page 18).
10. Operate log fire and perform remote controller recognition procedure (refer to
„Recognition Signal‟ on page 12).
Gas Valve Receiving Antenna LHEC30 (Procedure 14)
Wear Personal Protective Equipment when conducting step 3 of this
procedure to reduce the risk of electric shock. Refer to Rheem Safety
Procedure on electrical testing.
1. Isolate power and gas supplies to the log fire and open front lower access louvre.
2. Remove two nuts retaining transformer cover and lift out transformer cover.
3. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the transformer that voltage is not present.
4. Disconnect antenna spade terminal from gas valve and remove antenna.
5. Complete reassembly in reverse order of above.
6. Operate log fire and check remote controller operation. If remote controller does not
operate perform the remote controller recognition procedure (refer to „Recognition
Signal‟ on page 12).
Transformer LHEC30 (Procedure 15)
Wear Personal Protective Equipment when conducting step 3 of this
procedure to reduce the risk of electric shock. Refer to Rheem Safety
Procedure on electrical testing.
1. Isolate power and gas supplies to the log fire and open front lower access louvre.
2. Remove two nuts retaining transformer cover and lift out transformer cover.
3. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the transformer that voltage is not present.
4. Mark and disconnect wiring from transformer.
5. Remove four screws retaining transformer to transformer supporting bracket and
withdraw transformer through front of log fire louvre opening.
6. Complete reassembly in reverse order of above.