Specifications

TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A
D.O.I: 17/01/2008
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
26
Fault Finding Chart 4
YES
4
Is
gas inlet
pressure within
spec?
YES
NO
Refer to section on „Checking Gas Inlet
Pressure‟. Refer to Specification Table
for gas pressures.
Is
pilotstat knob
operated
correctly?
After successful ignition of
the pilot the pilotstat knob
must be rotated to
the „On‟ position.
Advise customer.NO
Does
pilot stay
lit?
YES
3
NO
NO
2
NO
Is
burner gas
pressure within
spec?
Replace gas valve.NO
Are burner
injectors
blocked?
YES
Clean or replace
burner injectors.
YES
NO
Refer to section on „Checking Burner
Gas Pressure‟. Refer to Specification
Table for gas pressures.
Is
burner feed pipe
blocked?
Is
burner manifold
blocked?
NO
YES
Clean or replace burner
manifold feed pipe.
Remove blockage from
burner manifold.
Replace gas valve.
YES
NO
Does
gas valve LED
indicate 3 or 8
flashes?
Does
pilot
ignite?
2.1
YES
YES