Specifications

TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A
D.O.I: 17/01/2008
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
22
Fault Finding Chart 2
YES
NO
Advise customer.
YES
Does
piezo ignitor
push button
operate?
2
Does
ignition plug
generate a
spark?
Replace piezo ignitor.
When pushed piezo
ignitor should produce
an audible „click‟
Does
piezo wire
generate a
spark?
NO
Test 1
NO
Is
ignition plug
gap set at
3mm?
YES
Replace ignition plug.YES
Does
ignition plug
generate a
spark?
Adjust ignition plug
gap to 3mm.
NO
Is gas
isolation valve
on?
YES
Turn gas isolation valve on.NO
YES
Is
Pilotstat knob
operated
correctly?
YES
Rotate pilotstat knob to the
„Pilot‟ position then depress
and hold in whilst attempting
to light pilot.
NO
Is
local/remote
switch set on
„Local‟?
The local/remote selector
switch must be set on „local‟
when lighting the pilot.
Set switch to „Local‟.
The local/remote selector switch
is located on the gas valve
NO
Is gas
inlet pressure
within spec?
Refer to section on „Checking Inlet Gas
Pressure‟. Refer to Specification Table
for gas pressures.
NOYES
YES Adjust pilot flame.
Is
pilot injector
blocked?
NO
Refer to section on „Adjusting
the Pilot Flame‟.
Is pilot
flame adjusted
correctly?
YES
Clean or replace
pilot injector.
YES
Is
pilot feed pipe
blocked?
NO
Clean or replace
pilot feed pipe.
YES
Replace gas valve.NO
NO
Does
gas valve LED
indicate 3 or 8
flashes?
NO
2.1
YES
Refer to section on
„adjusting the ignition
plug gap‟