SERVICE INSTRUCTIONS Gas Fireplace & Gas Log Fire TM036 Revision: A Published: January 08 LHEC30 RFSDV34 This document is stored and maintained electronically by Service.
Contents Safety Warning .................................................................................................................... 3 Introduction .......................................................................................................................... 3 Model Identification .............................................................................................................. 3 Specifications...................................................................................
Safety Warning The purpose of this service manual is to provide sufficient information to allow a person with the skills as required by the Regulatory Authorities to carry out effective repairs to a Vermont Gas Fireplace or Gas Log Fire in the minimum of time. Safety precautions or areas where extra care should be observed when conducting tests outlined in this service manual are indicated by print in bold italics and/or a warning symbol. Take care to observe the recommended procedure.
Specifications Specification Power supply Electrical connection Gas input – NG Gas input – P Output Heating Capacity (cool climate) Colour Heating type Circuit resistance (overall A - N) Fan resistance Gas valve gas connection Gas valve resistance (A – N) Transformer resistances Transformer voltages Thermopile 1 voltage (generated) Thermopile 2 voltage (generated) Pilot flame adjustment level Ignition plug gap Heater external dimensions (mm) Weight Minimum flue length Maximum flue length Blocked flue switch
Fluing To comply with the requirements of AS5601 the LHEC30 gas fireplace and RFSDV34 gas log fire must be flued. The LHEC30 is certified for a minimum flue length of 3.7 m and a maximum flue length of 10.7m whilst the RFSDV34 is certified for a minimum flue length of 3m and a maximum flue length of 12m.
Wiring Diagrams Wiring Diagram – LHEC30 & RFSDV34 When installing the RFSDV34 the draught hood adapter (draught diverter) supplied with the log fire MUST be installed. The draught diverter has an inbuilt „blocked flue safety switch‟ which MUST be wired in series with thermopile circuit 1 by the installing technician. The log fire must not be operated unless the draught diverter is installed and the blocked flue switch wired as per the installation instructions & wiring diagram shown below.
Components and Their Function Transformer The transformer converts the incoming supply voltage from 240 VAC to 115VAC. Fan The fan moves air from outside the log fire through the back of the heater and out through the front louvre via an air flow chamber. The air flow chamber is separated from the combustion chamber and is heated by conduction. The heated air is then circulated by the fan (convection heating).
The burner manifold directs gas from the gas valve to the front and rear burner injectors. The burner manifold has an aeration shutter which controls the air gas ratio for delivery to the injectors. The aeration shutter is preset and the position remains the same for both gas types. Injectors Both log fires have three injectors (pilot, burner front and burner rear). The pilot injector delivers gas to the pilot whilst the burner injectors deliver gas from the burner manifold to the burner for combustion.
6. Antenna: The antenna receives transmissions from the remote control. The antenna should hang in free air away from grounded (earthed) metal. 7. Gas type plug: There are two gas type plugs available, one for NG and one for Propane. This plug determines the gas type the gas valve operates on (refer to „Gas Type Conversion Procedure‟ on page 51 for more information). 8. Pilot adjustment screw: This screw is utilised to adjust the pilot flame height by altering the gas pressure to the pilot.
6. After successful ignition the pilotstat knob (4) is then manually turned to the „ON‟ position allowing gas entry via the gas valves (2) internal main valve to the burner (11). The burner (11) and fan (12) will now operate on full flame and full speed and both the internal pilot valve solenoid and internal main valve solenoid are held open by the voltage generated by thermopile 1 (8) and thermopile 2 (9), provided the blocked flue switch (10) remains closed. 7.
Operational Flow Chart On Operation Manual Off Operation Plug In Power On E A Fault rectified Isolate Power Gas valve fault (1) Initial check normal? NO Thermopile fault YES Local/Remote selector switch manually set to „Local‟ (if on „Remote) Wait until LED stops indicating 1 flash NO Remote controller reset to auto or on? Pilot gas valve open Pilotstat knob manually depressed & held in Piezo igniter manually pushed generating spark at igniter Pilot gas valve closed B C Fan on previous re
Lighting Instructions 1. Ensure the LOCAL/REMOTE selector switch on the gas valve is set on LOCAL. 2. Remove the log fire glass door. 3. Turn the pilotstat knob to the PILOT position, push the pilotstat knob down and hold it in the depressed position. The pilot valve is now open and will allow gas to flow to the pilot. 4. Push and release the piezo igniter until the pilot flame is established.
On (Manual) Mode Press and release the „Mode‟ button until „On‟ is displayed on the controller. After a two second delay the burner and fan will turn on and operate on the previously used settings. The information shown on the diagram opposite will be displayed on the remote controller display. To adjust the main burner flame level press and release the flame button. The flame icon will be displayed along with the current flame level setting.
If the set point temperature is now higher than the room temperature the optimum flame and fan levels will automatically be selected to reach or maintain the set point temperature. These levels (of modulation) will depend upon the differential between the set point temperature and the room temperature i.e. larger differential = higher flame and fan levels. For example: If there is a differential of 2.
Preventative Maintenance It is suggested for peak performance that the log fire be serviced annually. Servicing is to be performed by qualified persons. 1. Remove log set and larva rocks. 2. Clean the glass panel(s) with a non-ammonia based household cleaner and warm water (gas fireplace glass cleaner is recommended for use as a cleaning agent). Check the glass and gasket for cracks or damage and replace the glass frame assembly and/or gasket if necessary.
Common Faults When a complaint is lodged about the performance of a gas fireplace or gas log fire there are a number of causes that should be checked and eliminated. In an attempt to pinpoint the most likely cause it is important to discuss with the customer their reasons for the complaint, the duration of the problem, any change in circumstances or usage and recent weather conditions.
Fan Speed or Flame Height Cannot be Adjusted by Remote Controller If the fan speed and flame height cannot be adjusted by the remote controller check the following: 1. Ensure the three pin plug is plugged in and power is available at the power point. Without power the log fire can still be lit and the burner will operate on high flame, however the fan will not operate and flame height cannot be adjusted utilising the remote controller. 2.
Adjusting the Pilot Flame When lit, the pilot should produce a flame 10 – 13mm vertically high that impinges evenly across both thermopiles. The pilot flame can be adjusted by rotating the pilot adjustment screw on the gas valve which will alter the gas pressure to the pilot. Unscrew and remove the outer cap and turn the internal screw clockwise to decrease the pilot flame or anti-clockwise to increase the pilot flame.
Error Code 3 Error code 3 is a thermopile related fault and is indicated by three 0.5 second flashes separated by a 30 second off period between each series of flashes. If this fault occurs check the following: 1. Disconnect power and ensure all thermopile spade connectors are pushed on firmly and are making contact. Check blocked flue switch to ensure it is not open circuit. Restore power. If error code 3 is still displayed move on to step 2. 2.
Fault Diagnosis Sequence (General Fault Finding Chart) General Fault Finding Chart Fault Pilotstat knob cannot be operated YES 1 YES 2 YES 3 YES 4 NO Pilot will not ignite NO Pilot will not stay lit NO Burner will not ignite NO Burner ignites but goes out 5 NO Fan does not operate YES 6 YES 7 Noisy Log fire 8 NO Remote controller does not operate log fire NO TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A D.O.
Fault Finding Chart 1 1 Does gas valve LED indicate 3 or 8 flashes? 2.1 YES NO Does gas valve LED indicate 1 flash? YES NO Wait until the gas valve LED stops flashing Replace the gas valve Can the pilotstat knob be operated? NO YES Replace the gas valve Thermocouples were still hot from previous operation. Normal operation Fault Finding Test 1 Test 1 Warning - Ensure power is isolated before conducting this test. 1.
Fault Finding Chart 2 2 Does gas valve LED indicate 3 or 8 flashes? NO 2.1 YES The local/remote selector switch Is is located on the gas valve local/remote NO switch set on „Local‟? Is Pilotstat knob operated correctly? YES YES NO Rotate pilotstat knob to the „Pilot‟ position then depress and hold in whilst attempting to light pilot.
Fault Finding Chart 2.1 & 2.2 2.1 Is the gas valve LED indicating 3 flashes? YES Are all thermopile spade terminals pushed on firmly? Reconnect thermopile spade terminal(s) firmly. NO 2.2 No: Error code 8 is indicated (8 flashes) Notes (1) RFSDV34 blocked flue switch can be manually reset < 218ºC. LHEC30 auto resets < 132ºC. YES Test 2A for LHEC30 or Test 2B for RFSDV34 Is blocked flue switch open? Is flue blocked or partially blocked? YES NO NO Rectify flue and/or flue cowl fault.
Fault Finding Chart 3 3 Does gas valve LED indicate 3 or 8 flashes? NO 2.1 YES Does pilot ignite? YES 2 NO Is Pilotstat knob operated correctly? YES Pilotstat knob must be held in the depressed position and not released until after the gas valve LED provides 1 flash indication. NO Did gas valve LED indicate 1 flash? YES Retry lighting 3 times ensuring that the Pilotstat knob is not released until 5 seconds after the LED gives 1 flash indication.
Fault Finding Tests 2A – 4 Test 2A – LHEC30 Test 2B – RFSDV34 Warning – Log fire may be hot. Ensure log fire has sufficiently cooled before conducting this test. Warning – Log fire and flue may be hot. Ensure log fire has sufficiently cooled before conducting this test. Disconnect wiring from blocked flue switch. Using a multimeter on the ohms scale, measure between the two terminals of the blocked flue switch. Disconnect wiring from blocked flue switch.
Fault Finding Chart 4 4 Does gas valve LED indicate 3 or 8 flashes? Does pilot ignite? NO 2.1 YES Does pilot stay lit? YES 2 NO YES 3 NO Is pilotstat knob operated correctly? NO After successful ignition of the pilot the pilotstat knob must be rotated to the „On‟ position. YES Refer to section on „Checking Gas Inlet Pressure‟. Refer to Specification Table Is for gas pressures. gas inlet NO pressure within spec? Advise customer. YES Refer to section on „Checking Burner Gas Pressure‟.
Fault Finding Chart 5 5 Does gas valve LED indicate 3 or 8 flashes? NO 2.1 YES Refer to section on „Checking Gas Inlet Pressure‟. Refer to Specification Table Is gas for gas pressures. NO inlet pressure within spec? Refer to section on „Checking Burner Gas Pressure‟. Refer to Specification Is Table for gas pressures. burner gas NO YES pressure within spec? Advise customer. Replace gas valve.
Fault Finding Chart 5.1 & 5.2 5.1 5.2 Note: RC = Remote Controller (1) Is RC flame level „0‟? YES (1) Is RC room temp > or = set temp? Room temp must be > or = to set temp for burner to operate. NO NO YES Notes (1) When room temp = set temp burner may be on or off. (1) Is RC room temp = set temp? YES Increase RC set temp to 1º > room temp & wait for 1 minute.
Fault Finding Chart 6 6 (1) (1) Is Log fire plugged into power point & switched on? Plug Log fire into power point and switch on. NO Notes (1) Log fire will light and burner will operate on high flame without 240V power supply however fan and some remote controller functions will not operate. YES 6.
Fault Finding Tests 5 – 6 Test 5 Test 6 Warning – „Live‟ equipment wear Personal Protective Equipment when conducting this test. Warning - Ensure power is isolated before conducting this test. Ensure power point is switched on and using a multimeter on the AC voltage scale, measure between the 3 pin sockets on the power point. The following results should be obtained: Mark and disconnect wiring from the fan and using a multimeter on the ohms scale, measure between the two fan terminals.
Fault Finding Tests 7A – 8B Test 7A – LHEC30 Test 7B – RFSDV34 Warning - Ensure power is isolated before conducting this test. Mark and disconnect wiring from the transformer and using a multimeter on the ohms scale, measure between terminals 1 and 5 of the transformer (transformers primary winding). Warning - Ensure power is isolated before conducting this test.
Fault Finding Chart 6.1 & 6.2 6.1 6.2 Note: RC = Remote Controller Notes (1) This refers to the wording next to the fan icon (remote controller on auto but fan manually overridden) (2) When room temp = set temp fan may be on or off. (1) Is RC fan setting on manual? YES NO (2) Is RC fan level „0‟? YES (2) Is RC room temp > or = set temp? NO Room temp must be > or = to set temp for fan to operate. YES Increase RC set temp to 1º > room temp & wait for 1 minute.
Fault Finding Chart 6.3 Electrical Insulation Test 6.3 megger between the log fire 3 pin plug active pin and earth. Then megger between the 3 pin plug neutral pin and earth. Is either reading below 1 mega-ohm? NO Faulty power circuit. Advise customer to have electrician check household power circuit. Is the reading below 1 mega-ohm? YES Replace transformer. Is the reading below 1 mega-ohm? YES Replace fan assembly. Is the reading below 1 mega-ohm? YES Replace gas valve.
Fault Finding Chart 7 7 Does gas valve LED indicate 3 or 8 flashes? Notes (1) Log fire will light and burner will operate on high flame without 240V power supply however fan and some remote controller functions will not operate.
Fault Finding Chart 8 8 Is the noise a creaking and/or cracking noise? YES It is normal for heating appliances fabricated from steel to give off some expansion and/or contraction noises during the start-up or cool down cycle. YES Remove fan obstruction. YES Replace fan assembly. NO Is the fan obstructed? NO Is the fan or fan motor motor noisy? Check for vibration noise caused by loose component.
Log Assembly – LHEC30 (Procedure 2) 1. Remove front glass assembly (refer to procedure 1). 2. Remove logs and larva rock from burner. Reassemble as follows: 3. Place rear centre log KR24 on rear log bracket. Locate the two holes in bottom of log over the centre two bracket studs. 4. Place left log KR22 on rear log bracket. Locate the two holes in bottom of log over the left two bracket studs. 5. Place right log KR23 on rear log bracket. Locate the two holes in bottom of log over the right two bracket studs.
Pilot Assembly – LHEC30 (Procedure 4) 1. Remove sheet metal base assembly (refer to procedure 3). 2. Mark and disconnect thermopile wiring at gas valve. Note: Mark wiring to ensure thermopiles are reconnected in their original location. 3. Disconnect ignition plug wiring by unplugging at electrical joining connector. 4. Unscrew pilot feed pipe nut at gas valve and remove pilot feed pipe from gas valve. 5. Remove screw retaining pilot heat shield to bracket and remove pilot heat shield. 6.
Burner – LHEC30 (Procedure 9) 1. 2. 3. 4. 5. 6. 7. Isolate power and gas supplies to the log fire. Remove front glass assembly (refer to procedure 1). Remove log assembly and larva rock from burner (reverse procedure 2). Remove two screws retaining log bracket to log fire rear and remove log bracket. Remove screw retaining burner manifold cover and remove burner manifold cover. Remove two screws retaining burner hold down brackets to burner base.
Gas Valve – LHEC30 (Procedure 13) 1. Remove the sheet metal base (refer to procedure 3). 2. Mark and disconnect all gas valve wiring. Note: Mark wiring to ensure thermopiles and components are reconnected in their original location. 3. Disconnect ignition plug wiring by unplugging at electrical joining connector. 4. Unscrew pilot feed pipe nut at gas valve and remove pilot feed pipe from gas valve. 5. Unscrew burner feed pipe nut at gas valve elbow and remove burner feed pipe from gas valve. 6.
Fan Assembly – LHEC30 (Procedure 16) Wear Personal Protective Equipment when conducting step 3 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing. 1. Isolate power and gas supplies to the log fire and open front lower access louvre. 2. Remove two nuts retaining transformer cover and lift out transformer cover. 3.
Component Replacement Procedures – RFSDV34 Removing the Glass Frame Assembly – RFSDV34 (Procedure 19) Only glass and gaskets approved by Raypak Australia may be used for replacement. The use of substitute glass and/or gaskets will void all warranties. Under no circumstances is the log fire to be operated without the glass frame assembly or with a broken glass panel or gasket. Replacement of the glass including the gasket is to be performed by a licensed and qualified person.
Pilot Assembly – RFSDV34 (Procedure 22) Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing. 1. Isolate power and gas supplies to the log fire and remove front lower access panel (refer to procedure 21). 2. Confirm with a multi-meter between Active and Neutral, then Active and Earth, then Neutral and Earth terminals of the transformer that voltage is not present. 3.
Pilot Injector – RFSDV34 (Procedure 25) 1. 2. 3. 4. Isolate power and gas supplies to the log fire. Remove glass frame assembly (refer to procedure 19). Remove log assembly and larva rock from burner (reverse procedure 20). Unscrew and remove top section of pilot light (section above bracket) from pilot assembly. 5. Remove injector from top section of pilot light. 6. Complete reassembly in reverse order of above. 7. Test for gas leaks at all unions using soapy water solution.
Burner Feed Pipe – RFSDV34 (Procedure 29) 1. Remove the burner (refer to procedure 27). 2. Unscrew burner feed pipe nut at gas valve and remove burner feed pipe from gas valve. 3. Remove heat resistant sealing compound from burner feed pipe aperture in log fire base. 4. Remove retaining screw holding burner manifold bracket to log fire base and withdraw burner manifold and burner feed pipe through aperture in log fire base. 5.
Gas Valve Receiving Antenna – RFSDV34 (Procedure 32) Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing. 1. Isolate power and gas supplies to the log fire and remove front lower access panel (refer to procedure 21). 2. Confirm with a multi-meter between Active and Neutral, then Active and Earth, then Neutral and Earth terminals of the transformer that voltage is not present. 3.
Blocked Flue Switch – RFSDV34 (Procedure 35) If the log fire has been recently operated the flue will be extremely hot. A serious and significant burn hazard exists. Ensure the log fire is not operating and that the flue has sufficiently cooled before attempting to remove the blocked flue switch. 1. Remove two screws retaining blocked flue switch cover to draught diverter and withdraw blocked flue switch cover and blocked flue switch from draught diverter. 2. Disconnect wiring to the blocked flue switch. 3.
Exploded View 1 – LHEC30 TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A D.O.I: 17/01/2008 This document is stored and maintained electronically by 47 Service.
Replacement Parts List – LHEC30 (Exploded View 1) Item 1 1a 1b 1c 1d 1e 2 3 4 5 6 7 12 13 15 21 24 25 26 27 28 30 34 35 36 40 41 42 43 44 45 46 47 49 50 52 Not Shown Description Log Set Complete Log Rear Left Log Rear Right Log Rear Centre Log Front Left Log Front Right Larva Rock Burner Package A Larva Rock Burner Package B Burner Assembly (includes ceramic tiles) Ceramic Tile - Burner (single) Injector Burner Front - NG Injector Burner Front - Propane Injector Burner Rear - NG Injector Burner Rear - Prop
Exploded View 2 – RFSDV34 TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A D.O.I: 17/01/2008 This document is stored and maintained electronically by 49 Service.
Replacement Parts List – RFSDV34 (Exploded View 2) Item 1 1a 1b 1c 1d 1e 1f 2 3 4 5 6 7 8 11 12 13 14 15 18 19 20 24 27 28 29 30 31 32 34 40 Not Shown Description Log Set Complete Log Ember Bed Log Front Left Log Front Right Log Rear Log Top Left Log Top Right Larva Rock Burner Package A Burner Assembly (includes ceramic tiles) Ceramic Tile - Burner (single) Injector Burner Rear - NG Injector Burner Rear - Propane Injector Burner Front - NG Injector Burner Front - Propane Injector Pilot - NG Injector Pilo
Gas Type Conversions Both the LHEC30 and RFSDV34 are gas type convertible between Natural and Propane gas. The gas type conversion procedure is identical for both log fires as are the gas type conversion kits.
Warranty Raypak Majestic LHEC30 Gas Fireplace & RFSDV34 Gas Log Fire Warranty (Australia only) *Rheem Australia will: a) Repair or, if necessary replace any Raypak LHEC30 Gas Fireplace or RFSDV34 Gas Log Fire, or b) Replace any component (or, if necessary, arrange the installation of a LHEC30 Raypak Gas Fireplace or RFSDV34 Gas Log Fire, which falls within the Warranty Periods specified in the installation and operating instructions, in accordance with the subject table, conditions and exclusions.
Document Revision History Title: Vermont Log Fire Service Instructions Revision A Document Nº: TM036 Details of change Service Manual Issued for Gas Fireplace & Gas Log Fire TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A D.O.I: 17/01/2008 This document is stored and maintained electronically by D.O.I. 01/08 53 Service.