Operating instructions

11
Radiance
®
Direct Vent Gas Heater
20306759
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
B
CFM145a
DV Termin Location
5/01/01 Rev. 12/05/01
sta
INSIDE
CORNER DETAIL
A
G
CFM145a
V
V
V
V
V
V
V
V
N
General Venting Information - Termination Location
A = Clearance above grade, veranda, porch, 12" (30 cm) 12" (30 cm)
deck, or balcony
B = Clearance to window or door that may be 6" (15 cm) for appliances 6" (15 cm) for appliances
opened < 10,000Btuh (3kW), 12" (30 cm) < 10,000 Btuh (3kW), 9"
for appliances > 10,000 Btuh (3kW) and (23 cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36" (91 cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12" (30 cm) for
appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12" (305 mm) recommended to 12" (305 mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soft located
above the terminal within a horizontal 18" (458 mm) 18" (458 mm)
distance of 2’ (610mm) from the center
line of the terminal
E = Clearance to unventilated soft 12" (305 mm) 12" (305 mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91 cm) within a height of 15’ (5 m) 3’ (91 cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5 m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91 cm) 3’ (91 cm)
J = Clearance to nonmechanical air supply inlet 6" (15 cm) for appliances < 10,000 6" (15 cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12" (30 cm) for < 10,000 Btuh (3kW), 9"
other appliances appliances > 10,000 Btuh (3kW) and < (23 cm) for appliances > 10,000
100,000 Btuh (30kW), 36" (91 cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12" (30 cm) for
appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83 m) 3’ (91 cm) above if within 10’
(3 m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13 m)† 7’ (2.13 m)†
driveway located on public property
M = Clearance under veranda, porch, deck or 12" (30 cm)** 12" (30 cm)**
balcony
N = Clearance to any other obstruction within a horizontal distance of 18" (450 mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
** only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Stoves are certied as part of the appliance, with clearances tested and approved by the list-
ing agency.
3. Vermont Castings Group assumes no responsibility for the improper performance of the appliance when the venting system does
not meet these requirements.
Canadian Installations
1
US Installations
2
Fig. 11 Vent termination clearances.