H. Inspect the Venting System
The replace venting system is designed and constructed to
develop a positive ow adequate to remove ue gases to the
outside atmosphere. See replace installation instructions.
A spillage test must be made before the installed
appliance is left with the consumer
• Close all doors and windows in the home.
• Light the log set.
• After three minutes, test with a smoke match, smoke
candle, stick incense or cigarette one inch below the top of
the opening (lintel) moving across the full width. If spillage
(smoke drawn into the room) occurs, it will most likely be
near the top, outside corners.
Possible Cures if Spilling Occurs
• The damper should be fully open.
• The replace opening needs to be reduced by adding a
drop panel across the top under the lintel.
• The air supply from outdoors needs to be increased. Open
the outside air kit if the appliance is so equipped, or crack
open a door or window.
• If necessary, seek expert advice. Do not operate this
appliance.
Cleaning
Fire Risk
Explosion Risk
Inspect external vent cap regularly.
• Ensure no debris blocks cap.
• Combustible materials blocking cap may
ignite.
• Restricted air flow affects burner
operation.
WARNING