Operating instructions

8
75D0004
MLDV Series Gas Fireplace
3" Minimum
FP1978
gas connection

Figure 46 -
Gas Connection
Cap
Approved Flexible
Gas Line
CSA Design-Certied Equipment
Shutoff Valve with 1/8" NPT Tap*
Sediment Trap/Drip Leg

From Gas Meter
(4.5" w.c. to 10.5" w.c. Pressure)

From External Regulator
(11" w.c. to 13" w.c. Pressure)
 The gas line connection may be made using 1/"
rigid tubing or an approved ex connector. Since some
municipalities have additional local codes it is always best
to consult your local authorities and the current edition of
the National Fuel Gas Code ANSI.Z3.1, NFPA54. In
Canada CSA-B149 (1 or ) Installation Code.
A listed manual shutoff valve must be installed upstream of
the appliance. Union tee and plugged 1/8" NPT pressure
tapping point should be installed upstream of the appliance.
Figure 46
 Install main gas valve (equipment shutoff
valve) in an accessible location. The main gas valve is for
turning on or shutting off the gas to the replace.
Check your building codes for any special requirements for
locating equipment shutoff valve to replaces.
Tee Joint
Pipe Nipple

       


      



    

     

Figure 46
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess seal-
ant in pipe could result in clogged burner system valves
We recommend that you install a sediment trap/drip leg in
supply line as shown in Figure 46. Locate sediment trap/
drip leg where it is within reach for cleaning. Install in piping
system between fuel supply and burner system. Locate
sediment trap/drip leg where trapped matter is not likely
to freeze. A sediment trap collects moisture and contami-
nants and keeps them from going into the burner system
gas controls. If sediment trap/drip leg is not installed or is
installed wrong, burner system may not run properly.