Operating instructions
75D0004 13
MLDV Series Gas Fireplace
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length of vent pipe for
the type of termination you choose. It is also important to
note the wall thickness.
Select the amount of vertical rise desired. All horizontal run
of venting must have 1/4" rise for every 1" of run towards
the termination below 7
1
/ feet of vertical rise. With 7
1
/ feet
or more vertical rise off top of replace, the horizontal run
may run level. NEVER run vent piping downward.
You may use up to three 90° elbows in this vent congu-
ration. Refer to Horizontal Termination Congurations on
Pages 17 and 18.
Measure the distance from the replace oor to the ceil-
ing. Add the ceiling thickness, the vertical rise in an attic
or second story, and allow for sufcient vent height above
the roof line.
You may use two 45° elbows in place of a 90° elbow.
You must follow rise to run ratios when using 45° elbows.
The appliance is approved for use with three 90° elbows
maximum or a combination of 90° and 45° elbows up to a
maximum of 70°.
Z\x
For two-story applications, restops are required at each
oor level. If an offset is needed in the attic, additional pipe
and elbows will be required.
You may use a chase with a vent termination with exposed
pipe on the exterior of the house. Refer to Installing Vent
System in a Chase below. If pipe is enclosed in chase, it
is not exposed.
It is very important that the venting system maintain its bal-
ance between the combustion air intake and the ue gas
exhaust. Certain limitations apply to vent congurations
and must be strictly followed.
A chase is a vertical boxlike structure built to enclose
venting that runs along the outside of a building. A chase
is required for such venting.










