Connect the Gas Supply Line
This appliance should only be connected
by a qualified gas technician. Test to
conrm manifold pressures as specied
below.
The Intrepid Heater and the individual shutoff valves
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.5 kPa).
The Intrepid Heater must be isolated from the gas
supply piping system by closing the individual
manual shutoff valve during any pressure testing
of the gas supply piping system at test pressure
equal to or less than 1/2 psig.
There must be a gas shutoff between the stove and
the supply.
In order to connect Natural Gas, use a tting with
3/8” NPT nipple on the valve side and 1/2” natural
gas supply line with a minimum input of 21,000
BTUs at a minimum inlet pressure of 5.5” w.c.
In order to connect Propane, use a tting with 3/8”
NPT nipple on the valve side and 1/2” propane gas
supply line with a minimum input of 21,000 BTUs
at a minimum inlet pressure of 11.0” w.c.