Operating instructions
9
Chateau™ Decorative Gas Appliance
20007172
General Venting
Your fireplace is approved to be vented either through
the side wall, or vertical through the roof.
• Only CFM Corporation venting components
specifically approved and labelled for this fire-
place may be used.
• Venting terminals shall not be recessed into a wall or
siding.
• Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be
any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24" (610mm) from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent
accidental blockage of venting system. When using
snow blowers, make sure snow is not directed towards
vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on following
page.
PILOT
HONEYWELL IGNITION MODULE
WHITE
BLACK
BLACK
NOVA SIT 822 VALVE
HI
LO
120 VAC RTN
WHITE
GREEN
BLACK
120 VAC HOT
BLACK
WHITE
24 VAC RET
40VA TRANSFORMER
24 VAC HOT
BLACK
WHITE
WALL SWITCH
WHITE
1 2 3 5 6 8 9
MV MV/VP PV GRD 24V SENSE SPARK
24V
WHITE
BLACK
To Receptacle
Supplied
in Valve Box
FP1367
Fig. 10 Honeywell ignition module.