Specifications
DFS Series Vent Free Fireplace
32
71D0532
1. Locate combustion air assembly at an exterior location
which is not likely to be accidentally blocked in any man-
ner. Locate assembly a min. of 12" above the snow line
to prevent blockage by snow accumulation.
2. Never mount the combustion air inlet assembly in a
garage or storage area where combustible fumes such
as gasoline might be drawn into the replace.
3. Combustion air can be drawn from the crawl space un-
der a house when an adequate supply of air is provided
by open ventilation.
4.
FP2459
OA basement install
FP2459
8' Max.
FP2460
OA slab install
Inlet Grille in
Soft
(Overhang)
FP2460
FP2461
above basement
Duct Extended
to Miss Joint
FP2461
FP2462
OA corner install
Inside
Wall
Outside
Wall
FP2462
5. Locate air supply inlet at least 3' away from any appli-
ance vent terminal.
6. Avoid extremely long runs and numerous turns in the
duct leading from the replace to the combustion air
assembly. These conditions increase the resistance to
the free ow of air through the duct. Refer to Figures
33 through 36 for methods of installing the outside air
for combustion assemblies.