When tightening the joint to the valve, hold the valve
securely to prevent movement.
Test all gas joints from the gas meter to the heater valve
for leaks using a gas analyzer or soap and water solution
after completing connection.     

Check the gas pressure with the appliance burning and
the control set to .

Figure 10
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or three turns
and then place tubing to pressure gauge over test point
(Use test point “OUT” closest to control knob). After taking
pressure reading, be sure and turn captured screw clock-
wise rmly to re-seal. Do not over torque. Check for gas
leaks.
FP2448
millivolt valve
Test Port
“Out”
FP2448





The millivolt valve is a self-powered combination gas control


1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall
switch or thermostat. At the other end, connect one
wire to TP/TH and one wire to TH, or connect the wall
switch/thermostat to the two male (0.25") terminals on
the left side of the unit. The color of the wires does not
matter.
