- Vermont Castings Direct Vent Gas Fireplace Installation Instructions and Homeowner's Manual DVT38S2IN

4
Chateau™ Direct Vent Gas Fireplace
20011957
Y
D
A
B
C
E
Y
X
LU584
Locating unit
DVT38S2
3/17/04 djt
Locating Your Fireplace
LU584-1
Fig. 2 Locate gas fireplace.
A) Flat on wall B) **Island C) *Room divider
D) *Flat on wall corner E) Chase installation
Y) 6” minimum
Note (Fig. 2):
** Island (B) and Room Divider (C) installation is possible as long
as the horizontal portion of the vent system (X) does not exceed 20’
(610cm). See details in Venting Section.
* When you install your fireplace in (C) Room divider or (D) Flat on
wall corner positions (Y), a minimum of 6” (152mm) clearance must
be maintained from the perpendicular wall and the front side edge of
the fireplace.
Fireplace Dimensions
Fig. 1 Fireplace specifications and framing dimensions for DVT38S2.
Finished Wall 24
¹⁄₂” (622 mm)
for Flush Install 16” (406 mm)
I.D. Minimum Clearance to
Combustibles
Standard Framing
NOTE: Noncombustible insula-
tion may be placed behind the
facing material.
Only
Noncombustible
Material in
This Area
Exterior Side
(If installed on
outside wall)
Interior
Side