Technical data

With the help of the ENTER button [12] the menu point is confirmed and the following
message is displayed:
INTERFACE
SEL : [RS 232C]
On pressing cursor buttons “” and “” [13] the desired interface GPIB or RS 232C is set.
The new setting RS 232C is saved with the ENTER button [12] and the following message
appears on the display [5]:
RS 232C
RATE: [24ØØ Bd]
On pressing cursor buttons “
” and “” [13] the selected transmission rate from 12ØØ Bd to
96ØØ Bd is set. The new setting is saved with the ENTER button [12] and the following
message appears on the display [5]:
RS 232C
PROT: [RTS/CTS]
On pressing cursor buttons “
” and “” [13] the communication protocol can be changed.
With the help of the ENTER button [12] the current protocol is saved and the settings are
finished.
After switching off the settings are saved.
7.2 Transition: Remote Control Local Control
On transmission of the command REN from the personal computer the power supply unit is in
the state of REMOTE CONTROL which is indicated by the LED REMOTE [14]. Afterwards
control of the unit by the local control elements is not possible (except LOCAL button [14]).
On changing to remote control the outputs of sources A and B are deactivated.
There are several ways of switching from remote control to local control of the unit:
- by transmission of the command GTL (Go To Local) from the PC,
- by pressing the LOCAL button [14] on the power supply unit if the unit keyboard
has not been locked by the command LLO (Local Lock Out),
- by switching off and on the power switch [1].
The following enquires and instructions can be transmitted and received by the PC even when
the unit is on local control:
*IDN?,*CLS,*ESR?,*ESE,*ESE?,*STB?,*SRE,*SRE?,ERR?,DER?.
23
Operating Instructions PN 300
1/99