GENERAL
Input Power Class 2; 12 to 24 Vdc, loop powered (polarity
insensitive)
Maximum Current Draw 29 mA
Output 2-wire transmitter; user selectable 4 to 20 mA
(clipped & capped)*
Surge Damping Electronic; 5-second averaging
Zero Adjust Pushbutton auto-zero terminals
Housing Material White powder-coated aluminum
PRESSURE RANGES (SELECTABLE)
0 to 50 psi (0 to 3.45 barg)
(Gauge)
0-5/10/25/50 psid (0-0.34/0.69/1.72/3.45 bard)
(Differential)
0 to 100 psig (0 to 6.89
barg) (Gauge)
0-10/20/50/100 psid (Differential)
(0-0.69/1.38/3.45/6.89 bard) (Differential)
0 to 250 psi (0 to 17.24 bar)
(Gauge)
0-25/50/125/250 psid (Differential)
(0-1.72/3.45/8.62/17.24 bard) (Differential)
SENSOR
Accuracy @ 25 °C** Range A, B, C: ±1% F.S.; Range D: ±2% F.S.***
Media Compatibility Media compatible with 17-4 PH stainless steel
Long Term Stability ±0.25% per year
Proof Pressure Max. 2x F.S. range
Burst Pressure Max. 5x F.S. range
Temperature
Compensated Range
0 to 50 °C (32 to 122 °F); TC Zero <±1.5% of
product F.S. per sensor ; TC Span<±1.5% of
product F.S. per sensor, (2 sensors per unit)
Media Temperature Limits -20 to 85 °C (-4 to 185 °F); 0 to 90% RH
non-condensing
* Minimum input voltage: 250 Ω loop = 12 Vdc; 500 Ω loop = 17 Vdc
**Accuracy combines linearity, hysteresis, and repeatability.
***FS is defined as full span of selected range in bi-directional mode.
EMC Conformance - Low voltage directive 2014/35/EU; EMC directive 2014/30/EU.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power
adaptor with proper surge protection (EN 61000-6-1 specification requirements).
APPLICATIONS
• Monitoring and controlling
pump differential pressure
• Chiller/boiler differential
pressure drop
• CW/HW system differential
pressure
The PW2 Series 2-wire, 4 to 20 mA wet pressure transducers incorporate
microprocessor profiled sensors for exceptional accuracy and reliability.
Easy to use and designed to provide exceptional installation savings,
the PW2 Series is ideal for measuring pressure across pumps, filters,
heat exchangers, compressors, and other non-corrosive wet media
applications.
The optional pre-assembled bypass valve is designed for easy
maintenance and a one-step installation.
Jumper selectable
The jumper-selectable output
switch for normal (4 to 20 mA) or
reverse (20 to 4 mA) operation
provides application flexibility
Dual sensor
Dual sensor design for improved
overpressure tolerance
…
eliminates the requirement for
a bypass valve assembly in most
applications
Rugged
Rugged, die-cast enclosure
provides NEMA 4 sealing
High stability
Jumper-controlled electronic
surge dampening for high
stability
Selectable
Selectable differential units: psid
or bard
Zero calibration
Pushbutton zero calibration – no
trim pots to adjust
…maintain
accuracy and reduce callbacks
with automatic zero calibration
SPECIFICATIONS
Product Operating
Environment
-10 to 55 °C (14 to 130 °F); 0 to 90% RH
non-condensing
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
MICROPROCESSOR PROVIDES DIGITAL SIGNAL
CONDITIONING
• Noise rejection reduces
fluctuating readings due to
noise or turbulence
• Surge damping prevents false
alarms by averaging fast peaks
0
Actual Pressure
Digitally Conditioned Output
TIME
F.S.
PRESSURE
Noise Rejection
Surge Damping
Output Clamping
PW2xxxS
PW2xxxBP
800.354.8556
|
+1 503.598.4564
|
sales@veris.com
|
intl@veris.com
|
veris.com
PW2 SERIES
4 to 20 mA, 2-Wire Devices
Pressure Monitoring | Wet Media Differential Pressure Transducers