Install Instructions

ZL0064-0D Page 1 of 2 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0119
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing this product.
Turn o all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specied by the manufacturer, the protection
provided by the product may be impaired. No responsibility is assumed by the
manufacturer for any consequences arising out of the use of this material.
Installation Guide
Pressure Sensors
TM
Product Identication
Product Overview
The PG Series pressure transducers are compatible with a variety of HVAC and industrial applications, such as
refrigeration measurement, pneumatic pressure measurement, gas pressure measurement, pump inlet, and outlet
uid pressure. They are also compatible with extreme applications, such as aerospace and motor sports equipment.
Volt and mA output options ensure integration with building systems. A wide selection of pressure ranges oers
application exibility. The PG Series oers a stainless steel housing and all models are warranted for a period of ve
years.
PG Series
Gauge Pressure Sensors
Range
03 = 0 to 15 psig
04 = 0 to 25 psig
05 = 0 to 50 psig
06 = 0 to 75 psig
07 = 0 to 100 psig
08 = 0 to 250 psig
09 = 0 to 500 psig
PG
Wetted Material
Output
M = 4 to 20 mA
V = 0 to 10 Vdc
J = 0 to 5 Vdc
A
Contact factory for additional ranges not shown.
= 316L stainless steel
ELECTRICAL
Supply Voltage
Class 2; 12 to 30 Vdc
Output
0 to 5 Vdc (3-wire), 0 to 10 Vdc (3-wire) or 4 to 20 mA (2-wire)
Load Impedance
Volt models >10 kΩ
mA models 250 Ω with 12 Vdc min. supply voltage
mA models 500 Ω with 17 Vdc min. supply voltage
Standard Connection
Cable gland 59” (1.5 m) length
Pressure Port
1/4” NPT Male
PERFORMANCE AT 25 °C (77 °F)
Accuracy*
±0.5% FS
Media Compatibility
Fluids and gases compatible with 316L stainless steel
Pressure Cycles
>100 million cycles
Over Pressure
2.5x FS with no change in calibration
ENVIRONMENTAL
Shock
100G, 11 msec, 1/2 sine
Vibration
20G peak, 20 to 2400 Hz
EMI/RFI Protection
Yes
Rating
IP66
Operating Temp Range
-30 to 120 °C (-22 to 248 °F)
Compensated Temp Range
0 to 55 °C (32 to 130 °F)
Total Error Band Over Temp
3% of FS
Humidity
0 to 95% RH non-condensing
* Accuracy includes nonlinearity and hysteresis.