Specications (cont.)
TEMPERATURE TRANSMITTER OPTION
Sensor Type Solid state, integrated circuit
Accuracy ±0.2 °C (±0.4 °F) typical
Resolution 0.1 °C (0.1 °F)
Range 0 to 50 °C (32 to 122 °F)
DISPLAY MODELS
Touchscreen 61 mm (2.4 in), color, backlit, capacitive, 240x300 px
Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable
Timeout override: Display timeout*
Lockout override: Touchscreen/button lockout*
LCD 52mm (2.05 in), segmented with 3 buttons
Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable
Timeout override: Display timeout*
Lockout override: Touchscreen/button lockout*
SETPOINTS**
Temperature Setpoint 0 to 10V output
Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F)
Humidity Setpoint 0 to 10V output
Scale: 0 to 100% RH
Fan Speed Setpoint 0 to 10V output
O 0V, Auto 1.5V, Low 3.3V, Med. 6.7V, High 10.0V
OVERRIDE
Override Button Display models feature a momentary-to-ground override button
WIRING TERMINALS
Terminal Blocks Screw terminals, 18-24 AWG
Screw Terminal Torque 0.2 N-m (2.0 in-lbF) max.
WARRANTY
Limited Warranty 5 years
COMPLIANCE INFORMATION
Agency Approvals UL 916, European conformance CE: EN61000-6-2,
EN61000-6-3, EN61000 Series - industrial immunity,
EN 61326-1
FCC Part 15 Class B, REACH, RoHS, RCM (Australia), ICES-003 (Canada)
*DIP switch selectable.
** One setpoint type is selectable via DIP switch on display models only.