HW2 Series Installation Guide
Installation (cont.)
6. Set the DIP switches.
ON
1
2345678
Temp / RH-Fan Setpoint
Temp Range 1 / 2
RH / Fan Setpoint
Screen Timeout On/Off
Touch-Button Disable On/Off
mA / Voltage
5V / 10V
Unused
Unused
Switch Function Description
1 Output mode ON - 4-20mA output mode enabled
OFF - Voltage output mode enabled
2 Voltage output range* ON - 0-5V output range enabled
OFF 0-10V output range enabled
3 Unused Unused
4 Unused Unused
5 Setpoint output type ON - Temperature setpoint enabled (temp range selected on DIP switch 6)
OFF - RH or Fan Speed setpoint enabled (specic setpoint output type to be
selected on DIP switch 6)
Models without RH option select only temp or fan setpoint
6 Setpoint output temperature range or
RH/Fan Speed output type
Temperature setpoint (must be enabled on DIP switch 5)
ON - Temp range 1, 50 to 95 °F (10 to 35 °C) enabled
OFF - Temp range 2, 32 to 122 °F (0 to 50 °C) enabled
RH or Fan Speed setpoint (must be enabled on DIP switch 5)
ON - RH setpoint enabled
OFF - Fan Speed setpoint enabled
Models without RH option, set to OFF
7 Display times out and turns o after
6-10 seconds of touchscreen/button
press
ON - Display Timeout enabled
OFF - Display Timeout disabled
8 Touchscreen touch functions and
buttons are disabled
ON - Touchscreen touch/button functions disabled
OFF - Touchscreen touch/button functions enabled
* Only used with voltage output mode enabled.
7. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it
latches at the bottom.