Install Instructions
Z207935-0C Page 2 of 9 ©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0920
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
HW2 Series Installation Guide
Specications (cont.)
DISPLAY MODELS
Touchscreen 61 mm (2.4 in), color, backlit, capacitive, 240x300 px
Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable
Timeout override: Display timeout*
Lockout override: Touchscreen/button lockout*
LCD 52mm (2.05 in), segmented with 3 buttons
Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable
Timeout override: Display timeout*
Lockout override: Touchscreen/button lockout*
SETPOINTS**
Temperature Setpoint 0 to 10V output
Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F)
Humidity Setpoint 0 to 10V output
Scale: 0 to 100% RH
Fan Speed Setpoint 0 to 10V output
O 0V, Low 3.3V, Med. 6.7V, High 10.0V
OVERRIDE
Override Button Display models feature a momentary-to-ground override button
WIRING TERMINALS
Terminal Blocks Screw terminals, 18-24 AWG
Screw Terminal Torque 0.2 N-m (2.0 in-lbF) max.
WARRANTY
Limited Warranty 5 years
COMPLIANCE INFORMATION
Agency Approvals UL 916, European conformance CE: EN61000-6-2,
EN61000-6-3, EN61000 Series - industrial immunity,
EN 61326-1
FCC Part 15 Class B, REACH, RoHS, RCM (Australia), ICES-003 (Canada)
*DIP switch selectable.
** One setpoint type is selectable via DIP switch on display models only.