Engineering Data
Hawkeye Current Sensor Model H735
Engineering Specifications
1. The current sensor shall be induce powered from the monitored load
2. The current sensor shall combine a status sensor for monitoring positive
status, and a command relay for starting or stopping motors in a single
package
3. The current sensor shall have an integral N.O. command relay capable of
switching 10A Resistive, 3A Inductive @ 30VDC, 240 VAC
4. The current sensor shall have an auto adjusting operating range from 1-135 A
5. The current sensor shall provide visual indication (LED’s) for output status,
sensor power, and relay status
6. The current sensor shall have an adjustable trip set-point to +/- 1 % of the
range from -15 to 60 ° C
7. The current sensor shall be isolated to 600 VAC RMS
8. The current sensor shall have an adjustable mounting bracket for installation
flexibility
9. The current sensor output shall be N.O., Solid State, 0.1 A @ 30 VAC/DC
10. The current sensor hole size shall be 0.75” in diameter
11. The current sensor dimensions shall be (LxWxH)… 2.95”X2.65”X1.05”
12. The current sensor with integral command relay shall be a Hawkeye model
H735