Install Instructions

Z207932-0C Page 8 of 12 ©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0920
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
CW2 Protocol Series Installation Guide
Object Name Object Identifier Object Property
Display CO2* BV8 ACTIVE displays CO
2
level on Screen
INACTIVE removes CO
2
level from Screen
Display VOC* BV9 ACTIVE displays VOC level on Screen
INACTIVE removes VOC level from Screen
Screen Color Set* MSV 1 Selection for Screen Color Theme
Fan Speed* MSV 2 Fan Speed Selection
* Preserved during power outages.
Device Objects Table:
Object Name Object Identifier Object Property Description
Living Space Room Unit XXXXXXX Vendor_ID + nnn Object _Identifer (R/W) Unique value where nnn initially is the
MS/TP address
BACnet Protocol Implementation Conformance Statement
Vendor Name: Veris Industries
Product Name: Living Space Room Unit
Product Model: CW2XXXX
Application Software Version: LSA_APP_REV2.04.20
Firmware Revision: LSA_APP_REV2.04.20
BACnet Protocol Version : 1
BACnet Protocol Revision: 16
Product Description: Environmental Sensor
BACnet Standardized Device Prole (AnnexL):
BACnet Application Specic Controller (B-ASC)
List All BACnet Interoperatvility Building Blocks Supported(Annex K):
DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B
Data Link Layer Options: MS/TP (Clause 9), baud rates, 9600, 19200, 38400, 76800
Device Address Binding: Static Device binding is not supported.
Networking Options: None
Character Sets supported: ISO 10646 (UTF-8)
6. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it
latches at the bottom.
7. Install locking screw to secure cover in closed position.
Installation (cont.)