Install Instructions

Z207932-0C Page 6 of 12 ©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0920
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
CW2 Protocol Series Installation Guide
Example: No Parity, 19200 Baud
1 2 3 4 5 6 7 8
o o on o o o o o
None 19200 Baud Unused
Modbus Point Map
Function Codes:
Function Code Function
03 Read holding (RW) registers
04 Read input (RO) registers
06 Write single register*
16 Write multiple registers
01 Read coils
05 Write single coil
15 Write multiple coils
* Not supported.
All of these values correspond to BACnet objects with the same name. See the BACnet Conformance Statement for their
denitions.
Note that an attempt to write to “read only” holding registers will give an error and the entire write command will not be
executed even if writing to read/write locations were also requested. Exception code 2 is given in this case. “Preserved” means
the values is maintained through power outages.
32-Bit Input Registers (Read Only):
Register Description
1 Temperature reading in IEEE 32-bit oating point
3 Humidity reading in IEEE 32-bit oating point
5 CO reading in IEEE 32-bit oating point
7 VOC reading in 32-bit integer
9 Model (numeric representation of ASCII characters)
42 Serial number (numeric representation of ASCII characters)
32-Bit Holding Registers (Read/Write):
Register Description
1 Temperature setpoint
3 Humidity setpoint
5 Screen color set
7 Device name
40 Fan speed
Note: All holding registers are preserved during power outages.
Coils (Read/Write):
Register Description
2* CO stoplight
3* Touchbutton disable
4* Invoke CO calibration
5* Temperature (°C)
6 Occupancy override
7* Touch timeout
8* Display shows humidity
9* Display shows CO level
10* Display shows VOC level
*Preserved during power outages.
Installation (cont.)