CW2 Protocol Series Installation Guide
Installation (cont.)
4. Mount the backplate onto the wall using the screws provided.
Six screw holes available. Use
a minimum of two for secure
mounting.
5. Connect the wires to the screw terminals. Do not over-tighten the screws.
54321
RS-485 (+)
RS-485 (-)
POWER SUPPLY 20-30 Vdc, 24 Vac
CONTROL SYSTEM
COMMON
COMMON
+
-
POWER (+24)
Congure the device.
Address Configuration:
Each device on a single network must have a unique address. Set the DIP switch labeled “ADDRESS” to assign a unique address
before the device is connected to the network. If an address is selected that conicts with another device, neither device will be
able to communicate.