Owner's manual

flow
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Transmier: Analog, BTU,
Pulse and Protocol Output
DESCRIPTION
3x0 programmable transmitters are capable of converting the frequency signal from
any of our ow sensors to a preferred output type (analog, scaled pulse, protocol).
In addition to standard square wave signals, it can also accept a sine wave, making
it a versatile transmitter for numerous applications. The 310 and 320 oer analog
and scaled pulse output, respectively, while the 340 models oer communication
protocols (N2, BACnet/Modbus, or LonWorks), with energy (BTU) measurement
(appropriate software and programming cables are required for installation; see
Ordering Information).
APPLICATIONS
Converting sine/square wave signals to 4-20 mA and protocol
Increasing wire run length limit for ow sensors
Connecting ow sensors to BAS panels
FEATURES
Programmable (units of measure, calibration, etc.) using computer with
Windows-based operating system...save installation time in the eld by
pre-programming the device
Accepts sine wave input from a variety of other sources for application
exibility
Compact size...saves space in crowded enclusures
Communication protocols available on the 340 models
310 SPECIFICATIONS
Power Requirements Loop input voltage 9-35VDC
Input Frequency 0.4 Hz to 10 kHz
Load Resistance Max 750Ω@24VDC
Operating Temperature Range -29° to 70°C (-20° to 15F)
Storage Temperature Range -40° to 85°C (-40° to 185°F)
Accuracy ±0.04% of reading over entire span
Linearity 0.1% of full scale
320 SPECIFICATIONS
Power Requirements 12-30VACm 85mA max.; 12-40VDC, 30mA max.; Reverse and over voltage protected to 40VDC
Input Frequency 0.4 to 10 kHz
Transient Suppression Complies with IEC-801-4 electrical burst, fast transient specication
Pulse Output Isolated solid state switch in any standard or custom ow total units; Adjustable 50 msec to 1.0 sec pulse output width in 50 msec increments
Maximum Sinking Current 100mA@36VDC
Operating Temperature Range -29° to 70°C (-20° to 15F)
Storage Temperature Range -40° to 85°C (-40° to 185°F)
340 SPECIFICATIONS
Power Requirements 12-24VDC or 12-24VAC, 70mA max.
Flow Sensor Input Excitation voltage 3-wire sensors: 9.1VDC 500Ω source impedance
Frequency 4-10000 Hz
Temperature Sensor Input 10k Dale Thermistor (requires 2, sold separately)
Operating Temperature Range -29° to 70°C (-20° to 15F)
Storage Temperature Range -40° to 85°C (-40° to 185°F)
Units of Measure:
Flow Rate gpm, gph, l/sec, l/min, l/hr, ft3/sec, ft3/min, ft3/hr, m3/sec, m3/min, m3/hr
Total Flow gallons, liters, cubic feet, cubic meters
Energy Rate kBTU/min, kBTU/hr, kW, MW, hp, tons
Total Energy BTU, kBTU, MBTU, kWh, MWh, kJ, MJ
Converts Flow Signal To A
Linear 4-20mA Analog or
a Protocol Signal
310-00
Year
Warranty
1
320-00
340-00
NEW!
both bacnet
& modbus in
one btu
transmitter
3x0 SERIES
HQ0001785.D 01131