User Manual

flow
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Tee Meter, Brass
DESCRIPTION
Metal tee-style liquid ow sensor with cast brass housing ts 1/2” to 1.5” NPT. These
sensors are accurate, even at low ow rates. Use in conjunction with a Veris ow
monitor or transmitter for a complete ow monitoring system.
APPLICATIONS
Measuring liquid ow rates
Accounting for total accumulated ow
FEATURES
PPS electronics housing...highly durable
Six-bladed impeller design with a proprietary, non-magnetic sensing
mechanism...high accuracy and repeatability
Forward-swept impeller is less prone to fouling by water-borne debris...
reliable performance with minimal downtime
Operation and repeatability even at low ow rates
Signal can travel up to 2000 ft (609 m) between the sensor and the display unit
without the need for amplication
Supplied with 20 ft (6 m) of 2-conductor AWG 20 UL type PTLC cable
(105°C rated)
Sensors of similar type are interchangeable,...need for recalibration after
servicing or replacement...quick install and fast maintenance
SPECIFICATIONS
Maximum Pressure At 38°C (100°F) 400 psi; At 105°C (221°F) 325 psi
Wetted Materials UHMW-PE bearing, polyamide impeller, tungsten carbide shaft, EPDM O-rings
Recommended Flow 0.3 to 15 ft/sec (0.09 to 4.5 m/sec)
Accuracy ±1.0% of rate
Repeatability ±0.7% over recommended design ow range*
Linearity ±0.7% over recommended design ow range*
Rangeability 60:1
Output Frequency 0.8 to 80 Hz
* ≥10 upstream and ≥5 downstream straight pipe diameters, uninterrupted ow.
For Pipe Sizes 1/2” To 1.5” NPT
250BR0505-1211
Year
Warranty
1
250x SERIES
HQ0001781.B 01131