Datasheet
UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com
technicalspecification |
3 of 3
ELECTRICAL CHARACTERISTICS
ELAND PART NO. NO. OF CORES NOMINAL CROSS
SECTIONAL AREA
mm
2
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL OUTER
SHEATH THICKNESS
mm
NOMINAL OVERALL
DIAMETER
mm
NOMINAL
WEIGHT
kg/km
V0110001GR000 12 0.5 0.40 1 9.1 139
V0110011GR000 12 0.75 0.40 1 9.9 179
V0110021GR000 12 1 0.40 1.10 10.9 225
V0110031GR000 12 1.5 0.40 1.20 12.4 302
V0114001GR000 18 0.5 0.40 1.1 10.7 201
V0114 011G R 0 0 0 18 0.75 0.40 1.20 11. 9 230
V0114021GR000 18 1 0.40 1.20 12.9 324
V0114031GR000 18 1.5 0.40 1.40 14.8 446
V0114041GR000 18 2.5 0.50 1.60 18.2 704
V0118001GR000 25 0.5 0.40 1.2 12.9 285
V0118 011G R 0 0 0 25 0.75 0.40 1.30 14.3 372
V0118021GR000 25 1 0.40 1.40 15.7 462
V0118031GR000 25 1.5 0.40 1.60 18 627
V0118041GR000 25 2.5 0.50 1.90 22.3 997
V0122011GR000 34 0.75 0.40 1.50 16.3 492
V0122021GR000 34 1 0.40 1.60 17.9 617
V0122031GR000 34 1.5 0.40 1.70 20.2 833
V0122041GR000 34 2.5 0.50 2.10 25.2 1337
V0125021GR000 50 1 0.40 1.80 21 869
V0125031GR000 50 1.5 0.40 2 23.8 118 6
V0125041GR000 50 2.5 0.50 2.40 29.6 1898
V0126021GR000 61 1 0.40 1.90 22.7 1031
NOMINAL CROSS
SECTIONAL AREA
mm
2
CURRENT CARRYING CAPACITES 30°C
CONTINOUS LOADING
A
MAXIMUM RESISTANCE
OF CONDUCTOR AT 20°C
ohms/km
0.5 9 39
0.75 12 26
1 15 19.5
1.5 18 13.3
2.5 26 7.98
4 34 4.95
6 44 3.3
10 61 1.91
16 82 1.21
25 108 0.780
35 135 0.554
Find this product online: elandcables.com | Cables & Accessories
Veriflex | Veriflex YY PVC (YSLY) Control Cable
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.