Installation Instructions

20 21
The Thermostat is not controlling the HVAC unit.
Check if the HVAC unit is set to “External Thermostat” (Class 2) mode.
Verify the status of the red light on the Wireless Control Card;
The red light is off
The Wireless Control Card is not powered. Verify that the Wireless
Control Card is properly wired to the HVAC unit - specifically make
sure that the RED and the BLACK wires are properly connected;
If the red light is blinking with one (1) flash
The Wireless Control Card is powered but it is not communicating
with the thermostat, turn the thermostat off and on to re-initiate
the linking procedure.
In case of a Network Installation, re-link the thermostat and the
Wireless Control Card with the Network Programmer.
The red light is blinking with three (3) flashes.
The Wireless Control Card is communicating with the thermostat.
Verify that the Wireless Control Card is properly wired to the HVAC
unit and that equipment settings on a thermostat - compressor
type, electric heat and reversing valve - are properly configured.
Troubleshooting APPENDIX 1 - Energy Saving Presets
SCREEN
NUMBER
Level
0
Level
1
Level
2
Level
3
Level
4
Level
5
1
Fan Control Mode
AUTO
AUTO AUTO AUTO AUTO AUTO
2
1st Stage Differential Heat
0.5
0.5 0.5 0.5 0.5 0.5
3
2nd Stage Differential Heat
1
1 1 2 2 2
4
1st Stage Differential Cool
0.5
0.5 0.5 0.5 0.5 0.5
5
Guest Occupancy Threshold
0
5 5 5 5 5
6
Night Occupancy Threshold
1
1 1 1 1 1
7
Force 2nd Stage Heating After
30
30 30 30 30 30
8
Night Occupancy Start
18
19 20 21 22 23
9
Night Occupancy End
12
11 10 9 8 7
10
Recovery Time
0
15 20 25 30 0
11
Recovery Temperature Heat
70
69 68 67 66 65
12
Setback Delay - Heat
0
30 25 20 15 10
13
Minimum Setback Temperature
67
66 65 64 63 62
14
Setback Delay - Cool
0
30 25 20 15 10
15
Maximum Setback Tempera-
72
74 76 78 80 82
16
Recovery Temperature Cool
71
72 73 74 75 76
17
Minimum Set point
64
64 65 66 67 68
18
Maximum Set point
82
82 80 78 76 74
19
Temperature Control Mode
AUTO
AUTO AUTO AUTO AUTO AUTO
20
Auto Changeover Set Point
1
1 1 1 1 1
21
Auto Restore
OFF
ON ON ON ON ON
21
Setback Set Points
OFF
ON ON ON ON ON
22
Automatic Humidity Control
ON
ON ON ON ON ON
23
Temperature Calibration
0
0 0 0 0 0