User's Manual
28 29
TEMPERATURE RECOVERY TIME
00-60 (25*) Select the maximum time allowed for a PTAC unit to
attain temperature as defined by Heat and Cool “Recovery
Temperature”;
“Temperature Recovery Time” selected here and the actual
efficiency of the PTAC unit are used to calculate setback
temperatures. Calculated setback temperatures maximize
energy savings and at the same time ensure that a
comfortable room temperature (defined as Heat and Cool
“Recovery Temperature”) will be restored within the selected
“Temperature Recovery Time”.
Setting the “Temperature Recovery Time” to “00”, disables
temperature recovery. When temperature recovery is disabled,
thermostat will use the Minimum and Maximum Setback
Temperatures as setback setpoints.
Thermostat Settings
RECOVERY TEMPERATURE - HEAT
62-82 (66°F) Select the room temperature in °F that a PTAC unit will
have to attain within the selected “Temperature Recovery
Time” when there is a need for heating.
Thermostat Settings