User's Manual

35
15 – MAXIMUM SETBACK TEMPERATURE
72-92 (78°F* default setting) Select the “Maximum Setback
Temperature” in °F.
Setback temperature is calculated by measuring PTAC
unit’s ability to attain “Recovery Temperature - Cool” within
“Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to
“0”) or if setback temperatures have not yet been calculated,
the “Maximum Setback Temperature” value will be used as the
setback temperature for cooling.
If calculated setback temperature for air conditioning is higher
than “Maximum Setback Temperature”, then the “Maximum
Setback Temperature” will be used as setback temperature for
air conditioning.
This feature allows defining the maximum temperature in a
room when room is unoccupied and the thermostat is in the
setback mode.
Custom Energy Savings Settings