User's Manual

33
13 – MINIMUM SETBACK TEMPERATURE
52-72 (64°F* default setting) Select the “Minimum Setback
Temperature” in °F.
Setback temperature is calculated by measuring PTAC unit’s
ability to attain “Recovery Temperature - Heat” within
“Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to
“0”) or if setback temperatures have not yet been calculated,
the “Minimum Setback Temperature” value will be used as the
setback temperature for heating.
If calculated setback temperature for heating is lower than
“Minimum Setback Temperature”, then the “Minimum Setback
Temperature” will be used as setback temperature for heating.
This feature allows defining the minimum temperature in a
room when room is unoccupied and the thermostat is in the
setback mode.
Custom Energy Savings Settings