HRV 150 R Owner Manual
www.vents-us.com
2017/12
Tel: 888-640-0925
513-348-3853
Fax: 513-268-4597
Sales@ventsus.com
VentsUS.com
11013 Kenwood Road, Cincinnati, Ohio 45242
Performance ERV 150 (R) EC
Ext. Differential Pressure - in. WG
Ext. Differential Pressure - in. WG
Gross Airflow - CFM
Gross Airflow - CFM
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
020406080100 120 140160 180200
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
020406080 100 120140 160180 200
Supply
Exhaust
Supply
Exhaust
External Static Pressure Net Supply Air Flow
Gross Air Flow
Power
Supply Exhaust
Pa in. W.G. L/s cfm L/s cfm L/s cfm Watts
25 0.1 85 181 88 186 81 171 186
50 0.2 82 175 85 180 78 165 186
75 0.3 80 169 82 174 75 159 186
100 0.4 77 162 79 167 72 153 185
125 0.5 74 156 76 161 70 147 185
150 0.6 70 149 73 154 67 141 184
175 0.7 67 142 69 146 64 135 184
200 0.8 64 135 66 139 61 128 184
225 0.9 55 117 62 131 57 121 183
250 1 52 110 58 123 54 114 182
275 1.1 49 104 54 115 51 107 181
300 1.2 45 96 50 107 47 99 181
325 1.3 42 88 46 97 43 91 180
350 1.4 38 80 41 88 39 83 178
375 1.5 34 73 37 78 36 75 176
400 1.6 30 64 32 69 31 66 174
425 1.7 26 54 28 58 27 56 172
450 1.8 21 45 22 47 22 47 169
475 1.9 16 35 17 36 17 36 166
500 2 12 24 12 25 12 25 163
525 2.1 6 14 7 14 7 14 159
550 2.2 2 4 2 3 2 4 156
Supply Temperature Net Airflow
Average
Power
(Watts)
Sensible
Recovery
Efficiency
Apparent
Sensible
Effectiveness
Net
Moisture
Transfer
°C °F L/s cfm
HEATING
I 0 32 31 66 26 73 82 0.46
II 0 32 46 97 42 70 78 0.38
III 0 32 50 107 52 68 75 0.36
IV
V -25 -13 31 65 89 63 77 0.37
** Total Recovery Efficiency
COOLING VI 35 95 31 66 26 50.1 ** 68 0.42
Model Volts Max. Watts Max. Amps
ERV 150R EC 120V, 60Hz 186 2.5
Extract air
Supply air
Exhaust air
Intake air
Frigate HRV 150R EC, ERV 150R EC