HRV 150 R EC Specs
PRODUCT
SPECIFICATIONS
TECHNICAL
DATA
Tel: 888-640-0925
513-348-3853
Fax: 513-268-4597
Sales@ventsus.com
VentsUS.com
11013 Kenwood Road,
Cincinnati, Ohio 45242
Frigate ERV 150R EC
ENERGY RECOVERY VENTILATION
PERFORMANCE
EXTERNAL STATIC PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
POWER
SUPPLY EXHAUST
Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts
25 0.1 85 181 88 186 81 171 186
50 0.2 82 175 85 180 78 165 186
75 0.3 80 169 82 174 75 159 186
100 0.4 77 162 79 167 72 153 185
125 0.5 74 156 76 161 70 147 185
150 0.6 70 149 73 154 67 141 184
175 0.7 67 142 69 146 64 135 184
200 0.8 64 135 66 139 61 128 184
225 0.9 55 117 62 131 57 121 183
250 1 52 110 58 123 54 114 182
275 1.1 49 104 54 115 51 107 181
300 1.2 45 96 50 107 47 99 181
325 1.3 42 88 46 97 43 91 180
350 1.4 38 80 41 88 39 83 178
375 1.5 34 73 37 78 36 75 176
400 1.6 30 64 32 69 31 66 174
425 1.7 26 54 28 58 27 56 172
450 1.8 21 45 22 47 22 47 169
475 1.9 16 35 17 36 17 36 166
500 2 12 24 12 25 12 25 163
525 2.1 6 14 7 14 7 14 159
550 2.2 2 4 2 3 2 4 156
Gross Airow - CFM
Ext. Dierential Pressure - in. W.G.
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
0 20 40 60 80 100 120 140 160 180 200
Supply
Exhaust
SOUND
1.9 Sones (30 L/s @ 0.2 in. W.G.)
MODEL Volts Max. Watts Max. Amps
ERV 150 EC 120V, 60Hz 186 2.5
2018/10