Installer Setup
Dry Contact Operation (setup step 41 - 42)
Dry Contact Polarity (setup step 41)
Open (Normally Open) - The dry contact is open until the connected device
closes the circuit.
Dry Contact Use (setup step 42)
CONDENSATE - If CONDENSATE is selected when the dry contact is active, the
thermostat will lockout the compressor terminal(s) and “CONDENSATE
PAN OVERFLOW” will appear on the display.
OCCUPIED - If OCCUPIED is selected, when the dry contact is active, the
thermostat will be forced into the programmed occupied mode / setpoints
and the ‘occupied’ icon will blink. This setting is useful for allowing a twist
timer to force occupied settings.
FDD - If FDD is selected when the dry contact is active, “EQUIPMENT FAULT”
will appear on the display.
Holiday - If HOLIDAY is selected, when the dry contact is active, the thermostat
will be forced into the programmed unoccupied mode / setpoints and the
‘unoccupied’ icon will blink.
Wired Sensor Type - Specifies the use of the connected, wired sensor.
The choices are: Remote or Supply. The remote option allows control to the
sensor, the supply does not.
Fahrenheit or Celsius (setup step 39)
This feature allows the thermostat to display temperature in Fahrenheit or
Celsius.
Press Fan To Clear All Messages (setup step 45)
This feature allows the user to clear all current error messages from the
display.