User Guide
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform to
local and national electrical codes. Improper wiring or installation
may damage the sensor.
Recognize safety information. This is the safety alert symbol.
When the safety alert symbol is present on equipment or in the
instruction manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard that
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal injury
or property damage.
The Extra-Zone system is used to create a subzone within a larger
conditioned area. The subzone is created by controlling (opening or
closing) the dampers which send air into the subzone. The Extra-
Zone module can also be used to control ventilation to the zone.
For example, an Extra-Zone system is installed in an over-
conditioned conference room which gets too cold while other areas
of the building are being cooled. A person inside the room would set
the thermostat for Heat. The Extra-zone module compares the
thermostat demand (Heat), with the duct temperature (less than 80
degrees F), and closes the zone damper, keeping the room from being
overcooled.
The Venstar Extra-Zone system consists of 4 parts:
Field-supplied zone thermostat with power supply
Field-supplied zone damper
Duct sensor
Extra-Zone module
The zone thermostat determines the demand for the zone and sends
the information to the Extra-Zone module; it does not control the
HVAC equipment. The zone damper controls how much system air
is allowed into the zone. The duct sensor senses duct temperature
and sends information to the Extra-Zone module. The Extra-Zone
module takes the zone thermostat demand duct temperature
information and determines whether the zone damper will be open or
closed.
1. Install the field-supplied thermostat in the zone. Be sure to
follow all recommendations regarding thermostat location described
in the thermostat installation instructions.
2. Install the Extra-Zone module in a location near the supply duct and
damper. The duct sensor is pre-wired to the Extra-Zone module.
Make sure that the Extra-Zone module is placed close enough to the
desired duct sensor location.
3. Connect the thermostat to the Extra-Zone module. Connect the C,
R, W, Y, and G terminals of the thermostat to the C, R, W, Y, and G
terminals of the Extra-Zone module (see Fig. 1 on reverse side).
4. The power supply can be connected to the thermostat or the Extra-
Zone module. Connect the C and R terminals of the power supply to
the C and R terminals of the thermostat or the Extra-Zone module. Do
not connect separate power supplies to both devices.
5. If not already installed, install the field-supplied zone damper(s) in
the supply side duct(s), which will provide conditioned air to the zone.
6. Run the duct sensor from the Extra-Zone module to the supply duct
of the damper. Install the duct sensor in the supply duct a few feet
before the zone damper. If the duct temperature sensor wiring is not
long enough, use a 3-conductor thermostat cable (18 to 24 gauge).
This cable is NOT suitable for any length greater than 75 feet. Be
sure to wire cap and tape all connections.
7. Connect the Extra-Zone module to the damper(s). Connect the
BROWN wire from the Extra-Zone module to the COM terminal of
the damper. Connect the RED wire of the Extra-Zone module to the
OP (open) terminal of the damper. Connect the WHITE wire of the
Extra-Zone module to the CL (close) terminal of the damper (see
Fig. 1). Up to four dampers may be controlled by one Extra-Zone
module. ( see Fig. 2 for wiring multiple dampers).
Heating and Cooling Control
The zone thermostat is located inside the subzone and does not
directly control the HVAC unit. Duct temperature and zone thermostat
demand are compared to determine if the dampers will open or close.
(See Table 1 below.)
OVERVIEW
INSTALLATION
!
©Venstar Inc. 12/07
P/N 88-700 Rev. 2
OPERATION
Page 1
SAFETY CONSIDERATIONS
IMPORTANT: Read entire instructions before turning on
the thermostat.
INSTALLATION INSTRUCTIONS
ACC0450
MODEL
EXTRA-ZONE™
ACCESSORY
Call for cool
Open
Open
Open
Closed
Closed
Closed
Closed
Open
Call for heat
Call for heat
Call for cool
80 F or above
No demand,
Fan set to AUTO
No demand,
Fan set to ON
70 F or below
Less than 80 F
Greater than 70 F
70 F to 80 F
Below 70 F or above 80 F
70 F to 80 F
Below 70 F or above 80 F
THERMOSTAT
DEMAND
DUCT
TEMPERATURE
DAMPER
POSITION
Table 1
Extra-Zone Control Settings