Technical data
Operation TTR31, TTR35
14 Endress+Hauser
5.1.4 Basic settings
!
Note!
The function group 4-20 is only available if the 4 to 20 mA analog output (
0>.,) is selected in
the function group - or . under 6 or 6..
Function
group
Function Settings Description
Technical unit C
C6
Select technical unit:
°C, °F, K
Factory setting: °C
Configure zero
point
,M, Position adjustment:
within ±10 °C/K
(±18 °F) of the upper
range limit
7@ Accept zero point ,M, No settings possible (not
available in PC software)
Display
66
66
PV: measured value
display
PVRO: measured value
display rotated 180°
SP: set switch point
display
SPRO: set switch point
display rotated 180°
OFF: display off
OFFR: display off rotated
180°
Factory setting:
measured value (PV)
Damping:
display value,
output signal
,M, Measured value damping
with regard to display
value and output: 0 (no
damping) or 9 to 40 s (in
increments of 1 second)
Factory setting: 0 s