Technical information
Ultrasonic Level Sensor LUC-M**
Function and system design
DOCT-0805F 01/2010 185414
3
Function and system design
Measuring principle
E: empty distance; F: span (full distance); D: distance from sensor membrane - product surface;
L: level; BD: blocking distance
Time-of-flight method
The sensor of the LUC-M** transmits ultrasonic pulses in the direction of the product surface.
There, they are reflected back and received by the sensor. The LUC-M** measures the time t
between pulse transmission and reception. The instrument uses the time t (and the velocity of
sound c) to calculate the distance D between the sensor membrane and the product surface:
D = c x t/2
As the device knows the empty distance E from a user entry, it can calculate the level as follows:
L = E – D
An integrated temperature sensor compensates for changes in the velocity of sound caused by
temperature changes.
Interference echo suppression
The interference echo suppression feature on the LUC-M** ensures that interference echoes
(e. g. from edges, welded joints and installations) are not interpreted as a level echo.
Calibration
Enter the empty distance E and the span F to calibrate the device.
Blocking distance
Span F may not extend into the blocking distance BD. Level echoes from the blocking distance
cannot be evaluated due to the transient characteristics of the sensor.
Sensor BD Max. range fluids Max. range bulk materials
LUC-M10 0.25 m (9.8 in) 5 m (16.4 ft) 2 m (6.6 ft)
LUC-M20 0.35 m (13.8 in) 8 m (26.2 ft) 3.5 m (11.5 ft)
LUC-M30 0.6 m (23.6 in) 15 m (49.2 ft) 7 m (23 ft)
LUC-M40 0.4 m (15.7 in) 10 m (32.8 ft) 5 m (16.4 ft)
20 mA
100 %
4 mA
0 %
D
L
F
E
BD