Technical information

Ultrasonic Level Sensor LUC-M**
Installation conditions
DOCT-0805F 01/2010 185414
13
Installation conditions for
flow measurements
Install the LUC-M** at the inflow side, as close above the maximum water level H
max
as possible
(take into account the blocking distance BD).
Position the LUC-M** in the middle of the channel or weir.
Align the sensor membrane parallel to the water surface.
Keep to the installation distance of the channel or weir.
You can enter the "Flow to Level" linearisation curve ("Q/h curve") using via the on-site display.
Example: Khafagi-Venturi flume
Example: Triangular weir
1 x b
0
b
0
BD
H
max
Khafagi - Venturi - flume
direction of flow
inflow
outflow
empty calibr.
max
max
max
max
min. 3 H
H
min. 2 H
α
min. 2 H
BD
(=
full calibr.)
empty calibr.