Electrical installation
4.9 Other connections
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
73
Commissioning
When commissioning using the STARTER or AOP30, the sine-wave filter must be activated
by means of appropriate selection screenforms or dialog boxes (p0230 = 3), see section
"Commissioning".
The following parameters are changed automatically during commissioning.
Table 4- 18 Parameter settings for sine-wave filters with SINAMICS S150
Parameter Name Setting
p0230 Drive filter type, motor side 3: Siemens sine-wave filter
p0233 Power unit motor reactor Filter inductance
p0234 Power unit sine-wave filter
capacitance
Filter capacitance
p0290 Power unit overload response Disable pulse frequency reduction
p1082 Maximum speed Fmax filter / pole pair number
p1800 Pulse frequency Nominal pulse frequency of the filter (see
previous table)
p1802 Modulator mode Space-vector modulation without
overmodulation
p1909 Motor data identification, control word Rs measurement only
Note
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.