Operating instructions

Electrical installation
4.5 EMC-compliant design
Drive converter cabinet units
52 Operating Instructions, 10/2008, A5E00288214A
4.5 EMC-compliant design
The following section provides some basic information and guidelines that will help you
comply with the EMC and CE guidelines.
cabinet assembly
Connect painted or anodized metal components using toothed self-locking screws or
remove the insulating layer.
Use unpainted, de-oiled mounting plates.
Establish a central connection between ground and the protective conductor system
(ground).
Shield gaps
Bridge shield gaps (at terminals, circuit-breakers, contactors, and so on) with minimum
impedance and the greatest possible surface area.
Using large cross-sections
Use underground and grounding cables with large cross-sections or, better still, with litz
wires or flexible cables.
Laying the motor supply cable separately
The distance between the motor supply cable and signal cable should be > 20 cm. Do not
lay signal cables and motor cables in parallel to each other.
Use anti-interference elements
Lay an equalizing cable parallel to the control cable (the cable cross-section must be at
least 16 mm²).
If relays, contactors, and inductive or capacitive loads are connected, the switching relays
or contactors must be provided with anti-interference elements.
Cable installation
Cables that are subject to or sensitive to interference should be laid as far apart from
each other as possible.
All cables are to be laid as close as possible to grounded enclosure parts such as
mounting plates or cabinet frames. This reduces both noise radiation and interference
injection.
Reserve cores of signal and data cables must be grounded at both ends to achieve an
additional shielding effect.
Long cables should be shortened or laid in noise resistant areas to avoid additional
connecting points.