Operating instructions

Appendix
A.2 Parameter macros
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
515
Parameter macro p0700 = 6: Terminal block TM31 (70006)
This macro is used to set customer terminal block TM31 as the command source.
Table A- 3 Parameter macro p0700 = 6: Terminal block TM31
Sink Source
Parameter Description DO Parameter Description DO
p0840[0] ON/OFF1 Vector r4022.0 TM31 DI0 TM31
p0844[0] No OFF2_1 Vector 1 CU
p0845[0] No OFF2_2 Vector r0722.3 CU DI3 CU
p0848[0] No OFF3_1 Vector 1 Vector
p0849[0] No OFF3_2 Vector r0722.2 CU DI2 CU
p0806 Inhibit LOCAL mode Vector 0 Vector
p0810 Changeover CDS bit 0 Vector 0 Vector
p0852 Enable operation Vector r4022.4 TM31 DI4 TM31
p0854 Control request Vector 1 Vector
p0922 PROFIdrive PZD telegram
selection
Vector 999 Free telegram configuration
p1020 FSW bit 0 Vector r4022.1 TM31 DI1 TM31
p1021 FSW bit 1 Vector r4022.2 TM31 DI2 TM31
p1035 MOP raise Vector r4022.1 TM31 DI1 TM31
p1036 MOP lower Vector r4022.2 TM31 DI2 TM31
p1113 Direction of rotation reversal Vector 0 TM31
p1140 Enable RFG Vector 1 Vector
p1141 Start RFG Vector 1 Vector
p1142 Enable nsetp Vector 1 Vector
p2103 Acknowledge fault 1 Vector 0 Vector
p2104 Acknowledge fault 2 Vector r4022.3 TM31 DI3 TM31
p2106 Ext. fault_1 Vector r0722.1 CU DI1 CU
p2107 Ext. fault_2 Vector 1 Vector
p2112 Ext. alarm_1 Vector r0722.0 CU DI0 CU
p2116 Ext. alarm_2 Vector 1 Vector
p0738 DI/DO8 CU 1 +24 V CU
p0748.8 Invert DI/DO8 CU 0 Not inverted
p0728.8 Set DI/DO8 input or output CU 1 Output
p0739 DI/DO9 CU 1 +24 V CU
p0748.9 Invert DI/DO9 CU 0 Not inverted
p0728.9 Set DI/DO9 input or output CU 1 Output
p0740 DI/DO10 CU 1 +24 V CU
p0748.10 Invert DI/DO10 CU 0 Not inverted
p0728.10 Set DI/DO10 input or output CU 1 Output
p0741 DI/DO11 CU 1 +24 V CU
p0748.11 Invert DI/DO11 CU 0 Not inverted
p0728.11 Set DI/DO11 input or output CU 1 Output