A.2 Parameter macros
Drive converter cabinet units
512 Operating Instructions, 10/2008, A5E00288214A
Sink Source
Parameter Description DO Parameter Description DO
p1280 Vdc controller configuration (V/f) Vector 0 Disable Vdc-max controller Vector
p1300 Open-loop/closed-loop control
operating mode
Vector 20 Encoderless speed control Vector
p1911 Number of phases to be identified Vector 3 3 phases Vector
p2051[0] CI: PROFIBUS PZD send word Vector r2089[0] ZSW1 Vector
p2051[1] CI: PROFIBUS PZD send word Vector r0063 n-act Vector
p2051[2] CI: PROFIBUS PZD send word Vector r0068 I-act Vector
p2051[3] CI: PROFIBUS PZD send word Vector r0080 M-act Vector
p2051[4] CI: PROFIBUS PZD send word Vector r0082 P-act Vector
p2051[5] CI: PROFIBUS PZD send word Vector r2131 FAULT Vector
p2080[0] BI: PROFIBUS send status word 1 Vector r0899.0 Ready for switching on Vector
p2080[1] BI: PROFIBUS send status word 1 Vector r0899.1 Ready for operation Vector
p2080[2] BI: PROFIBUS send status word 1 Vector r0899.2 Operation Vector
p2080[3] BI: PROFIBUS send status word 1 Vector r2139.3 Fault Vector
p2080[4] BI: PROFIBUS send status word 1 Vector r0899.4 No OFF2 Vector
p2080[5] BI: PROFIBUS send status word 1 Vector r0899.5 No OFF3 Vector
p2080[6] BI: PROFIBUS send status word 1 Vector r0899.6 Switching on inhibited Vector
p2080[7] BI: PROFIBUS send status word 1 Vector r2139.7 Alarm active Vector
p2080[8] BI: PROFIBUS send status word 1 Vector r2197.7 No setpoint/actual value deviation Vector
p2080[9] BI: PROFIBUS send status word 1 Vector r0899.9 Control request Vector
p2080[10] BI: PROFIBUS send status word 1 Vector r2199.1 Comparison value reached Vector
p2080[11] BI: PROFIBUS send status word 1 Vector r1407.7 M/I/P limiting not active Vector
p2080[12] BI: PROFIBUS send status word 1 Vector 0 Vector
p2080[13] BI: PROFIBUS send status word 1 Vector r2129.14 No alarm for motor
overtemperature
Vector
p2080[14] BI: PROFIBUS send status word 1 Vector r2197.3 Clockwise Vector
p2080[15] BI: PROFIBUS send status word 1 Vector r2129.15 No Therm. alarm Power unit
overload
Vector
p2088 PROFIBUS Invert status word Vector B800h Vector
p2128[14] Select fault/alarm code for trigger Vector 7910 A7910: Alarm, motor
overtemperature
Vector
p2128[15] Select fault/alarm code for trigger Vector 5000 A5000: Therm. alarm Power unit
overload
Vector
p2153 Time constant revolutions actual
value filter
Vector 20 20 ms Vector
p0840[0] ON/OFF 1 A_INF r0863.1 Energize line contactor Vector
p2105 BI: 3. Acknowledge faults A_INF r1214.3 Automatic restart status – set
acknowledgement command
Vector
p1207 BI: WEA link, following DO A_INF r1214.2 Automatic restart status – restart
active
Vector
p4053[0] TM31 analog inputs, smoothing
time constant
TM31 0 0 ms TM31
p4053[1] TM31 analog inputs, smoothing
time constant
TM31 0 0 ms TM31