Operating instructions

Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
507
Table 12- 17 Version A, 500 V – 690 V 3 AC, part 6
Order number 6SL3710 7LG41-3AA0
Unit rating
- for I
L
at 50 Hz 690 V
1)
- for I
H
at 50 Hz 690 V
1)
- for I
L
at 50 Hz 500 V
1)
- for I
H
at 50 Hz 500 V
1)
- for I
L
at 60 Hz 575 V
2)
- for I
H
at 60 Hz 575 V
2)
kW
kW
kW
kW
hp
hp
1200
1000
1250
800
1000
1000
Output current
- Rated current I
N A
3)
- Base load current I
L
4)
- Base load current I
H
5)
- Max. current I
max A
A
A
A
A
1270
1230
1136
1845
Infeed/regenerative current
- Rated current I
N E
6)
- Maximum current I
max E
A
A
1142
1905
Max. current requirement
- Auxiliary 24 V DC supply
A
Internal
Connection voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
500 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 - 28.8)
Power loss kW 42.25
Cooling air requirement m
3
/s 2.6
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A) 77/79
Line connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
4 x 240
8 x 240
M12 (4 holes)
Motor connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
4 x 240
6 x 240
M12 (3 holes)
Protective conductor connection
Fixing screw
M12 (18 holes)
Max. motor cable length
shielded / unshielded
m
300 / 450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
2800
2000
600
Frame sizes
- Active Interface Module
- Active Line Module
- Motor Module
JI
JX
JX
Weight (without options), approx. kg 2408