Operating instructions
Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
501
Table 12- 14 Version A, 500 V – 690 V 3 AC, part 3
Order number 6SL3710 7LG32-6AA0 7LG33-3AA0 7LG34-1AA0
Unit rating
- for I
L
at 50 Hz 690 V
1)
- for I
H
at 50 Hz 690 V
1)
- for I
L
at 50 Hz 500 V
1)
- for I
H
at 50 Hz 500 V
1)
- for I
L
at 60 Hz 575 V
2)
- for I
H
at 60 Hz 575 V
2)
kW
kW
kW
kW
hp
hp
250
200
160
132
250
200
315
250
200
160
300
250
400
315
250
200
400
350
Output current
- Rated current I
N A
3)
- Base load current I
L
4)
- Base load current I
H
5)
- Max. current I
max A
A
A
A
A
260
250
233
375
330
320
280
480
410
400
367
600
Infeed/regenerative current
- Rated current I
N E
6)
- Maximum current I
max E
A
A
242
370
304
465
375
619
Max. current requirement
- Auxiliary 24 V DC supply
A
Internal
Internal
Internal
Connection voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
500 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 - 28.8)
Power loss kW 11.97 12.69 19.88
Cooling air requirement m
3
/s 1.19 1.19 1.96
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A) 75/77 75/77 77/79
Line connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
2 x 95
4 x 240
M12 (2 holes)
2 x 120
4 x 240
M12 (2 holes)
2 x 185
4 x 240
M12 (2 holes)
Motor connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
2 x 95
2 x 185
M12 (2 holes)
2 x 120
2 x 240
M12 (2 holes)
2 x 185
4 x 240
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Max. motor cable length
shielded / unshielded
m
300 / 450
300 / 450
300 / 450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
1600
2000
600
1600
2000
600
2200
2000
600
Frame sizes
- Active Interface Module
- Active Line Module
- Motor Module
GI
GX
GX
GI
GX
GX
HI
HX
HX
Weight (without options), approx. kg 892 892 1716